| Specification |
| Model |
INV1K |
INV2K |
INV3K |
| Power Rating |
1000VA/700W |
2000VA/1400W |
3000VA/2100W |
| Input |
Voltage |
Single-phase, grounded |
| Frequency |
50/60 Hz ± 5% |
| Power Factor |
Comply with EN60555-2 standard for 220/230V equipment |
| Output |
Voltage Deviation |
± 3% |
| Power Factor |
0.7 lag |
| Frequency Deviation |
± 0.5%
In battery mode or the input frequency deviation > ± 5%
In normal input condition, synchronizes with the input frequency < ± 5% |
| Distortion |
Full load (linear load) < 4% THD
Full load (nonlinear load) < 7% THD |
| Overload Capability |
>130%, 5 seconds
>105%, 60 seconds |
| Load Crest Ratio |
3:1 max |
| Transfer time |
2.5 ms typical 4ms max(AC INPUT to BYPASS mode) |
| 0ms (AC INPUT to BATTERY mode) |
| Operating environment |
Temperature |
0oC to 40oC |
| Humidity |
0 to 95%, non-condensing |
| Altitude |
< 1500M |
| Storage Temperature |
-15oC to 40oC |
| Battery |
Internal battery voltage |
48Vdc |
48Vdc |
48Vdc |
| LED indicators |
Status |
Line / Bypass / Inverter / Fault / Load Level / Battery Level |
|
|
| Packing Details |
| Model |
Q'TY/CTN |
MEAS(mm) |
N.W.(kg) |
G.W.(kg) |
CONTAINER(PCS/20'GP) |
| INV1K |
1 |
610x600x270 |
9 |
12 |
300 |
| INV2K |
1 |
12 |
15 |
| INV3K |
1 |
12.5 |
15.5 |
|
|
|